价格:面议
0
联系人:谷*
电话:
地址:中国浙江杭州市杭州高新(滨江)区滨安路1192号
产品规格:DH4,DB4-AA.DA.AV.DV
产品数量:20000000000000000000000 个
包装说明:**
关 键 词:DB4系列智能电流电压
发布时间:2007-12-07
| VOLTAGE AND AMPERE METER >> 4 DIGIT VOL AND AMP METER >> DH4 VOL AND AMP METER
FEATURES
1.HI&LO Setpoint compare.
2.Bright LED 14.2mmH(red)
3.Input 0-**(Current Transformer)can adjust
fullscale 0-9999,Input 0-75mV(Shunt Resistor)
can adjust fullscale 100-9999.
4.Isolation of photoelectric for analog output 4-20mA
1. ORDERING CODE
2. AC VOLTAGE MEASUREMENT
Model Code Range Resolution
Input Impedance Accuracy Input Protection
DH4I-PAV10 0-9.999V 1mV ≤2MΩ ±0.5%F.S±2Digit ≤750V
DH4I-PAV100 0-99.99V 10mV ≤2MΩ ±0.5%F.S±2Digit ≤750V
DH4I-PAV600 0-600.0V 100mV ≤2MΩ ±0.5%F.S±2Digit ≤750V
3. AC CURRENT MEASUREMENT
Model Code Range Resolution
Accuracy Input Protection
DH4I-PAA0.2 0-200.0mA 100uA ±0.5%F.S±2Digit ≤1A
DH4I-PAA2 0-2.000A 1mA ±0.5%F.S±2Digit ≤**
DH4I-PAA5 0-5.000A 10mA ±0.5%F.S±2Digit ≤7A
DH4I-PAA20 CT input 20A:** 10mA ±0.5%F.S±21Digit 1.2Per.F.S
DH4I-PAA50 CT input 50A:** 100mA ±0.5%F.S±2Digit 1.2Per.F.S
4. DC VOLTAGE MEASUREMENT
Model Code Range MAX.Resolution Input Impedance Accuracy Input Protection
DH4I-PDV0.1 0-99.99mV 10uV ≤2MΩ ±0.5%F.S±1Digit ≤20V
DH4I-PDV10 0-9.999V 1mV ≤2MΩ ±0.5%F.S±1Digit ≤750V
DH4I-PDV100 0-99.99V 10 mV ≤2MΩ ±0.5%F.S±1Digit ≤750V
DH4I-PDV600 0-600.0V 100mV ≤2MΩ ±0.5%F.S±1Digit ≤750V
5. DC CURRENT MEASUREMENT
Model Code Range MAX.Resolution Input Impedance Accuracy Input Protection
DH4I-PDA 0-±200.0mA 100uA ≤1Ω ±0.5%F.S±1Digit ≤1A
DH4I-PDA2 0-±2.000A 1mA ≤0.1Ω ±0.5%F.S±1Digit ≤**
DH4I-PDA5 0-±5.000A 1mA ≤0.05Ω ±0.5%F.S±1Digit ≤7A
DH4I-PDA20 Shut Resistor 20A:75mV 由用户配置的分流器确定 ±0.5%F.S±1Digit 1.2Per.F.S
DH4I-PDA50 Shut Resistor 50A:75mV 由用户配置的分流器确定 ±0.5%F.S±1Digit 1.2Per.F.S
Explain:1. All of meter are HI&LO control, and 4∽20mA Analog output .
2. Attention please: With AC C.T. of the second ampere is ** that input current are bigger than **.And AC P.T. of the voltage second is 100V,if input voltage are higher than 600V.
3. Attention please: With DC shut Resistor of the second voltage is 75mV that input current are bigger than **
6. SPECIFICATIONS
Input mode Single ended
A/D converter Dual slope
Sampling speed Abt.2.5sec
Response time 0.25sec
Dsiplay mode Red LED (14.2mmH)
Analog output 4-20mA 0.5%R.D±3Digital
Analog range Measuring range can adjust fullscale setting
Control output HI&LO Setpoint compare(AC 2A/250V)
Power supply AC110/220V 50Hz/60Hz
Power consumption ≤1.5VA
Dielectic Strength AC 1500V 1min
Insulation Res. DC 500V≥100MΩ
Frequency range 45Hz~400Hz
7. CONNECTION DIAGRAM
8. THE OUTSIDE DIMENSION
9. CAUTIONS
1.The meter must be heating 15 minutes with the power on before use.
2.Use in ambient temperatures of 0℃ to 40℃,humidifies of 85% R.H.
3.The meter alignment interval time is one year.
4.If the input ** is superimposed with high-frequency noise,use a High-pass filter in the input ** line.
5.Input wire should not be too long. If measured ** and meter is long, please use a 2-core shielded cable, and connect its outer shite to the LO side at a ** soure.
6.If the digit meter relay is not used for a long time. Please counect power supply once every three months, not less
than 4 hours each time.
特 点
◎ **型输入,由输入代码选择量程
◎ 上下限报警继电器输出(250 V/3 A)
◎ 可带 4-20 ma 光电隔离变送输出
◎ 可带 RS 485/RS232/ RS422 通讯口
◎ 开关电源模块,SMT贴片制造工艺
一、型号及含义
二、技术参数
输入方式
单端输入
A/D转换
双重积分
测量速度
约2.5次/秒
测量精度
0.5%F.S±2Digit
响应时间
0.25sec
显示方式
红色数码管(14.2mmH)
溢出显示
“UUUU”或“LLLL”
错误显示
“Err.”(当L>H时,即出现该错误)
频率范围
45Hz∽400Hz(仅对交流)
变送输出
4∽20mA(0.5%R.D±3Digit)
变送范围
测量范围之间任意设定
控制输出
上下限报警继电器输出 AC 3A/250V
通讯方式
RS-485或RS-232
电源
开关电源 AC 90∽265V 50Hz/60Hz
功耗
≤1.5VA
耐压
AC 1500V 1min
绝缘电阻
DC 500V >50MΩ
工作环境
0∽50℃,45%∽85%RH
三、输入方式代码选择
代 码
量 程
备 注
代 码
量 程
备 注
0
600V
5
200mA
1
100V
6
20mA
2
10V
7
**
3
2V
8
特殊订做
4
200mV
9
特殊订做
注意:1、DH4系列智能电流电压表分交流和直流两在类型。
2、10V、100V、600V使用同一输入端,200mV、2V使用同一输入端。
3、测量交流电流**以上,需配交流电流互感器,其次级输出为**,因而其输入代码选择5即可。
4、测量直流电流**以上,需配直流电流分流器,其次级输出为75mV,因而其输入代码选择4即可,其输入端使用200mV输入端即可。
5、输入代码8、9、为客户特殊订做输入代码,客户特殊订做,需提供具体参数。
四、接线图
五、外形及开孔尺寸
六、菜单功能操作
1、 上下限报警数值设定
注意:设定J1、J2继电器动作值,应依据如下三个原则:
①吸合值>释放值:测量值≥吸合值继电器吸合,测量值≤释放值继电器释合。
②吸合值<释放值:测量值≤吸合值继电器吸合,测量值≥释放值继电器释放。
③吸合值=释放值:继电器无动作。
吸合值不等于释放值,其之间的区域构成回程不动作区。回程不动作区直接影响继电器动作频繁程度,该区域越小,继电器动作越频繁,这将有利于提高控制精度,但不利于设备使用寿命。通常,报警1-3个字,使用中,还要根据现场情况,灵活掌握。
举例说明见下表
举 列
J 1
J 2
不动作区(字)
吸合值
释放值
吸合值
释放值
J1
J2
上下限报警:上限8000,下限7800
8000
7996
7800
7804
3
3
上上限报警:报警点分别为500,600
500
497
600
597
2
2
下下限报警:报警点分别为500,600
497
500
597
600
2
2
2、功能菜单的设定
注意:通常情况下,仪表测量值与显示值是一致的,那在这里将H设为仪表测量值上限, 将L设为仪表测量值下限。但在某特定情况下,测量值与显示值是不一致的,那么在这里须设置为显示值对应的上下限。另外,也可用这两个菜单作为仪表测量值修正菜单,亦即仪表测量值与实际测量值有误差时,可通过这两个菜单增加或减少数字来修正仪表测量值的上下限。
3、校准菜单的设定
七、 通讯协议 (略)
八、使用保存注意事项
1.使用前 ,仪表需通电予热15分钟.
2.适宜使用环境温度0~+40℃,相对湿度85%以下.
3.本仪表校准时间间隔为一年.
4.若输入信号伴随高频干扰,应在线里用高频过滤器.
5.输入导线不宜过长.如被测信号输出端与仪表距离不能缩短,请用双绞屏蔽线,屏蔽层与信号低端相连.
6.若长期存放未使用,请每三个月通电一次,通电时间不少于4小时.
| VOLTAGE AND AMPERE METER >> 4 DIGIT VOL AND AMP METER >> DB4 DIGIT VOL AND AMP METER
FEATURES
1.HI&LO Setpoint compare.
2.Bright LED 14.2mmH(red)
3.Input 0-**(Current Transformer)can adjust
fullscale 0-9999,Input 0-75mV(Shunt Resistor)
can adjust fullscale 100-9999.
4.Isolation of photoelectric for analog output 4-20mA
1. ORDERING CODE
2. AC VOLTAGE MEASUREMENT
Model Code Range Resolution
Input Impedance Accuracy Input Protection
DB4(I)-PAV10 0-9.999V 1mV ≤2MΩ ±0.5%F.S±2Digit ≤750V
DB4(I)-PAV100 0-99.99V 10mV ≤2MΩ ±0.5%F.S±2Digit ≤750V
DB4(I)-PAV600 0-600.0V 100mV ≤2MΩ ±0.5%F.S±2Digit ≤750V
3. AC CURRENT MEASUREMENT
Model Code Range Resolution
Accuracy Input Protection
DB4(I)-PAA0.2 0-200.0mA 100uA ±0.5%F.S±2Digit ≤1A
DB4(I)-PAA2 0-2.000A 1mA ±0.5%F.S±2Digit ≤**
DB4(I)-PAA5 0-5.000A 10mA ±0.5%F.S±2Digit ≤7A
DB4(I)-PAA20 CT input 20A:** 10mA ±0.5%F.S±21Digit 1.2Per.F.S
DB4(I)-PAA50 CT input 50A:** 100mA ±0.5%F.S±2Digit 1.2Per.F.S
4. DC VOLTAGE MEASUREMENT
Model Code Range MAX.Resolution Input Impedance Accuracy Input Protection
DB4(I)-PDV0.1 0-99.99mV 10uV ≤2MΩ ±0.5%F.S±1Digit ≤20V
DB4(I)-PDV10 0-9.999V 1mV ≤2MΩ ±0.5%F.S±1Digit ≤750V
DB4(I)-PDV100 0-99.99V 10 mV ≤2MΩ ±0.5%F.S±1Digit ≤750V
DB4(I)-PDV600 0-600.0V 100mV ≤2MΩ ±0.5%F.S±1Digit ≤750V
5. DC CURRENT MEASUREMENT
Model Code Range MAX.Resolution Input Impedance Accuracy Input Protection
DB4(I)-PDA 0-±200.0mA 100uA ≤1Ω ±0.5%F.S±1Digit ≤1A
DB4(I)-PDA2 0-±2.000A 1mA ≤0.1Ω ±0.5%F.S±1Digit ≤**
DB4(I)-PDA5 0-±5.000A 1mA ≤0.05Ω ±0.5%F.S±1Digit ≤7A
DB4(I)-PDA20 Shut Resistor 20A:75mV 由用户配置的分流器确定 ±0.5%F.S±1Digit 1.2Per.F.S
DB4(I)-PDA50 Shut Resistor 50A:75mV 由用户配置的分流器确定 ±0.5%F.S±1Digit 1.2Per.F.S
1)If you need excition 4~20mA Analog output meter, Please you need with "I" in forward meter. Example, DB3-AV20 isn't with
4~20mA Analog supply output, DB3I-AV20 is with 4~20mA Analog supply output. The other models are the same.
2)Attention please:With AC C.T of the second ampere is ** that input current are bigger than **.And AC P.T. of the voltage second is 100V,if input voltage are higher than 1000V.
3)Attention please: With DC Shut Resistor of the second voltage is 75mV that input current are bigger than **.
6. SPECIFICATIONS
Input mode Single ended
A/D converter Dual slope
Sampling speed Abt.2.5sec
Response time 0.25sec
Dsiplay mode Red LED (14.2mmH)
Analog output 4-20mA 0.5%R.D±3Digital
Analog range Measuring range can adjust fullscale setting
Control output HI&LO Setpoint compare(AC 2A/250V)
Power supply AC110/220V 50Hz/60Hz
Power consumption ≤1.5VA
Dielectic Strength AC 1500V 1min
Insulation Res. DC 500V≥100MΩ
Frequency range 45Hz~400Hz
7. CONNECTION DIAGRAM
8. THE OUTSIDE DIMENSION
9. CAUTIONS
1.The meter must be heating 15 minutes with the power on before use.
2.Use in ambient temperatures of 0℃ to 40℃,humidifies of 85% R.H.
3.The meter alignment interval time is one year.
4.If the input ** is superimposed with high-frequency noise,use a High-pass filter in the input ** line.
5.Input wire should not be too long. If measured ** and meter is long, please use a 2-core shielded cable, and connect its outer shite to the LO side at a ** soure.
6.If the digit meter relay is not used for a long time. Please counect power supply once every three months, not less
than 4 hours each time.
| 数显电流电压表 >> 4位智能电流电压表 >> DB4智能数显电流电压表
特点
◎ 上下限报警继电器输出
◎ 红色高亮数码管14.2mmH
◎ 输入0-**(电流互感器)可在0-9999间调整满刻度
◎ 输入75 mV(电流分流器)可在100-9999间调整满刻度
◎ 光电隔离模拟4-20mA变送输出
一、 型号及含义
二、 交流电压测量
型号
量程
分辩力 输入阻抗
测量不准确度
输入极限
DB4-PAV10
0-9.999V
1mA ≤ 2MΩ ±0.5%F.S±2digit 1.2 F.S
DB4-PAV100
0-99.99V
10mA ≤ 2MΩ ±0.5%F.S±2digit 1.2 F.S
DB4-PAV600
0-600.0V 100mA ≤ 2MΩ ±0.5%F.S±2digit 1.2 F.S
三、 交流电流测量
型号
量程
分辩力 互感器变比 测量不准确度
输入极限
DB4-PAA0.2
0-200.0mA
100uA
直接输入
±0.5%F.S±2digit 500mA
DB4-PAA5
0-5.000A
1mA
直接输入
±0.5%F.S±2digit 7A
DB4-PAA20
0-20.00A
10mA
20A:**
±0.5%F.S±2digit 1.2 F.S
DB4-PAA50
0-50.00A
10mA
50A:**
±0.5%F.S±2digit 1.2 F.S
DB4-PAA100
0-100.0A
100mA
100A:**
±0.5%F.S±2digit 1.2 F.S
DB4-PAA150
0-150.0A
100mA
150A:**
±0.5%F.S±2digit 1.2 F.S
DB4-PAA200
0-200.0A
100mA
200A:**
±0.5%F.S±2digit 1.2 F.S
四、 直流电流测量
型号
量程
分辩率 互感器变比
测量不准确度
输入极限
DB4-PDA0.02 0-20.00mA
10uA
直接输入
±0.5%F.S±2digit
100mA
DB4-PDA0.2 0-200.0mA
100uA
直接输入
±0.5%F.S±2digit
1A
DB4-PDA5 0-5.000A
1mA
直接输入
±0.5%F.S±2digit
**
DB4-PDA20 0-20.00A
10mA
20A:75mV
±0.5%F.S±2digit
1.2 F.S
DB4-PDA50 0-50.00A
10mA
50A:75mV
±0.5%F.S±2digit
1.2 F.S
DB4-PDA100 0-100.0A
100mA
100A:75mV
±0.5%F.S±2digit
1.2 F.S
DB4-PDA150
0-150.0A
100mA
150A:75mV
±0.5%F.S±2digit
1.2 F.S
DB4-PDA200 0-200.0A
100mA
200A:75mV
±0.5%F.S±2digit
1.2 F.S
五、 直流电压测量
型号
量程
分辩率
输入阻抗 测量不准确度
输入极限
DB4-PD0.1 0-99.99mV
10uV ≤2MΩ ± 0.5%F.S±2digit
2V
DB4-PDV10
0-9.999V
1mV ≤2MΩ ± 0.5%F.S±2digit
20V
DB4-PDV100
0-99.99V
10mV ≤2MΩ ± 0.5%F.S±2digit
500V
DB4-PDV600
0-600.0V
100mV ≤2MΩ ± 0.5%F.S±2digit
750V
说明:1.在测量交流电流时,如需要配置电流互感器其二次端额定电流**,在测量交流电压时,其互感器二次端额定电压100V,大于**电流输入时**另外配置电流互感器,以及**600V电压输入时**配置电压互感器。
2.在测量直流电流时,如需配置电流分流器其二次变比标准电压75mV,大于**电流输入时**另配分流器.
六、 技术参数
输入方式
单端输入
A/D转换
双重积分
测量速度
约2.5次/秒
响应时间
0.25sec
显示方式
红色数码管Red LED (14.2mmH)
变送输出
4-20mA 0.5%R.D±3Digital
控制输出
上下限报警继电器输出 (2A/250V )
电源
AC 110V/220V 50Hz/60Hz
功耗
≤1.5VA
耐压
AC 1500 1 min
绝缘电阻
DC 500V>50MΩ
频率范围
45Hz~400Hz
七、 连接图
八、 外形及开孔尺寸
九、菜单功能操作
1、上下限数值设定
2、校准菜单
十.使用保存注意事项
1、 使用前,仪表需通电予热15分钟。
2、 适宜使用环境温度0~+40℃,相对湿度85%以下。
3、 本仪表校准时间间隔为一年。
4、 若输入信号伴随高频干扰,应在线里用高频过滤器。
5、 输入导线不宜过长。如被测信号输出端与仪表距离不能缩短,请用双绞屏蔽线,屏蔽层与信号低端相连。
6、 若长期存放未使用,请每三个月通电一次,通电时间不少于4小时。